Lake Elizabeth Mutual Water Co.
CCR - PAGE 3 - SAMPLING RESULTS
Home
RATES AND FEES
HISTORY
2004 CONSUMER CONFIDENCE REPORT
Photos then
Fires
Fires in the area
Repairs
Down construction

TABLE 2
LEAD AND COPPER SAMPLING RESULTS
 
 
 
 
 
LEAD AND COPPER
 
NO. OF SMPLES COLLECTED
90TH PERCENTILE LEVEL DETECTION
NO. SITES EXCEEDING ACTION LEVEL
REGULATORY ACTION LEVEL
MCLG
TYPICAL SOURCE OF CONTAMINANT
LEAD
10
.6
0
15
2
Internal corrosion of household water plumbing; discharges from industrial manufactures and erosion of natural deposits.
COPPER ( ppm)
10
.43
0
1.3
0.17
Internal corrosion of household water plumbing; erosion, natural deposits; leaching from wood perservatives.
TABLE 3
SAMPLING RESULTS FOR SODIUM AND HARDNESS
 
 
 
 
 
CHEMICAL OR CONSTITUENT
SMPLE DATE
LEVEL DETECTED
RANGE DETECTIONS
MCL
PHG
(MCLG)
TYPICAL SOURCE OF CONTAMINANT
SODIUM
(ppb)
2004
57
 
None
None
Generally found in ground and surface water
HARDNESS
(ppm)
2004
192
 
None
None
Generally found in ground and surface water
TABLE 4
DETECTION OF CONTAMINANTS WITH A PRIMARY DRINKING WATER STANDARD
 
 
 
 
 
CHEMICAL 0R CONSTITUENT
(and reporting units)
SAMPLE DATE
LEVEL DETECTION
RANGE OF DETECTIONS
MCL
PHG
(MCLG)
TYPICAL SOURCE OF CONTAMINANT
NONE DETECTED
 
 
 
 
 
 
NONE DETECTED
 
 
 
 
 
 
TABLE 5
DETECTION OF CONTAMINANTS WITH A SECONDARY DRINKING WATER STANDARD
 
 
 
 
 
CHEMICAL OR CONSTITUENT
(and reporting units)
SAMPLE DATE
LEVEL DETECTION
RANGE OF DETECTION
MCL
PHG
(MCLG)
TYPICAL SOURCE OF CONTAMINANT
NONE DETECTED
 
 
 
 
 
 
NONE DETECTED
 
 
 
 
 
 

  

TABLE 6 - SAMPLING RESULTS SHOWING TREATMENT OF SURFACE WATER
 
Treatment Technique - required process intended to reduce the level of contaminants in drinking water:  Approved conventional treatment consisting of flocculation, sedimentation, tri-media filtration and disinfection. 
 
Turbidity Performance Standards - turbidity is a measurement of the cloudiness of the water and is a good indicator of water quality and filtration performance.  Turbidity results which meet performance standards are considered to be in compliance with filtration requirements. 
 Turbidity of hte filtered water must:
 1. Be less than or eagual to 0.5 NTU in 95% of measurements in     a month.
 2. Not exceed >1.0 NTU for more than eight consecutive hours.
 3. Not exceed 5.0 NTU at any time.
 
Lowest monthly percentage of samples that met Turbidity Standard No.1 = 100%
 
Highest single turbidity measurement during the year = 0.9NTU
 
The number of violations of any surface water treatment requirements = 0
 
SUMMARY INFORMATION FOR CONTAMINANTS EXCEEDING AN MCL OR AL OR A VIOLATION OF ANY TREATMENT OR MONITORING AND REPORTING REQUIREMENTS:    NONE
 
 
 
 
 

 

 

END OF CCR